Advanced commissioning
8.32 Line contactor control
Figure 8-81
If the line contactor feedback signal is not available for longer than the time set in p0861,
then the converter issues fault F07300.
Parameter
Number
r0046.0...n
p0860
p0861
r0863.0...1
p0867
p0869
p0870
Further information is provided in the parameter list.
356
Line contactor control via DO 0 with feedback signal via DI 3
Name
CO/BO: Missing enable signals
BI: Line contactor feedback signal
Line contactor monitoring time
CO/BO: Drive coupling status word / control word
Power unit main contactor holding time after OFF1
Configuration sequence control
BI: close main contactor
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Factory setting
-
863.1
100 ms
-
50 ms
0000 bin
0
SINAMICS G120C Converters