Corrective maintenance
10.2 Downloading the converter settings
6. Select menu "Parameter".
7. To start commissioning of the safety functions, set p10 = 95.
8. Enter the password for the safety functions in p9761.
9. To confirm the settings of the safety functions, set p9701 = AC.
10.To exit commissioning of the safety functions, set p10 = 0.
11.Back up the settings so that they are protected against power failure.
12.Switch off the converter power supply.
13.Wait until all LEDs on the converter are dark.
14.Switch on the converter power supply again.
15.Perform a reduced acceptance test.
You have replaced the converter and transferred the safety function settings from the
operator panel to the new converter.
10.2.2.5

Download from Smart Access

Overview
You can transfer the converter settings that are backed up on the digital terminal device back
into the converter.
396
Reduced acceptance after component replacement and firmware change (Page 417)