Siemens SINAMICS G120C Operating Instructions Manual page 246

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Advanced commissioning
8.12 Switching over the drive control (command data set)
You select the command data set using parameters p0810 and p0811. To do this, you must
interconnect parameters p0810 and p0811 with control commands of your choice, e.g. a
digital input.
Changing the number of command data sets
Up to 4 command data sets are possible.
1. Set p0010 = 15.
2. The number of command data sets is configured with p0170.
3. Set p0010 = 0.
You have changed the number of command data sets.
Copying command data sets
1. Set p0809[0] to the number of the command data set whose settings you wish to copy
(source).
2. Set p0809[1] to the number of the command data set into which you wish to copy the
settings.
3. Set p0809[2] = 1
4. The converter sets p0809[2] = 0.
You have copied the settings of a command data set into another command data set.
Example
244
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
SINAMICS G120C Converters