Advertisement

Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Motor data identification. Select the method which the converter uses to measure the data of
the connected motor:
The converter switches off the motor after the motor data identification has been completed.
The converter switches off the motor after the motor data identification has been completed.
Select this setting if the motor cannot rotate freely.
The converter switches off the motor after the motor data identification has been completed.
After the motor data identification, the motor accelerates to the current setpoint.
After the motor data identification, the motor accelerates to the current setpoint.
Complete the data entry for quick commissioning as follows:
1. Switch over the display using an arrow key:
2. Press the OK key.
You have entered all of the data that is necessary for the quick commissioning of the
converter.
5.4.5

Dynamic Drive Control

Function description
Select the motor standard:
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
130
: No motor data identification
: Measure the motor data at standstill and with the motor rotating.
: Recommended setting: Measure the motor data at standstill.
: Measure the motor data while the motor is rotating.
: Setting the same as
: Setting the same as
: IEC
: NEMA, US units
: NEMA, SI units
: Third-party induction motor
: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
 → 
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK