Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
Motor data identification. Select the method which the converter uses to measure the data of
the connected motor:
•
•
The converter switches off the motor after the motor data identification has been completed.
•
The converter switches off the motor after the motor data identification has been completed.
Select this setting if the motor cannot rotate freely.
•
The converter switches off the motor after the motor data identification has been completed.
•
After the motor data identification, the motor accelerates to the current setpoint.
•
After the motor data identification, the motor accelerates to the current setpoint.
Complete the data entry for quick commissioning as follows:
1. Switch over the display using an arrow key:
2. Press the OK key.
You have entered all of the data that is necessary for the quick commissioning of the
converter.
❒
5.4.5
Dynamic Drive Control
Function description
Select the motor standard:
•
•
•
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
•
•
130
: No motor data identification
: Measure the motor data at standstill and with the motor rotating.
: Recommended setting: Measure the motor data at standstill.
: Measure the motor data while the motor is rotating.
: Setting the same as
: Setting the same as
: IEC
: NEMA, US units
: NEMA, SI units
: Third-party induction motor
: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
→
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
SINAMICS G120C Converters