Installing
4.2 EMC-compliant setup of the machine or plant
Figure 4-3
Further information
Additional information about EMC-compliant installation is available in the Internet:
60612658)
4.2.2
Cables
Cables with a high level of interference and cables with a low level of interference are connected
to the converter:
• Cables with a high level of interference:
– Cable between the line filter and converter
– Motor cable
– Cable at the converter DC link connection
– Cable between the converter and braking resistor
• Cables with a low level of interference:
– Cable between the line and line filter
– Signal and data cables
42
Grounding and high-frequency equipotential bonding measures in the control cabinet
and in the plant/system
EMC installation guideline