Siemens SINAMICS G120C Operating Instructions Manual page 207

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Table 8-12
Parameter
p0015 = 17
Parameter
Parameter
r0722.0...n
p0840[C]
p1113[C]
p3330[C]
p3331[C]
r3333.0...n
p3334
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
8.5 Controlling clockwise and counter-clockwise rotation via digital inputs
Set two-wire control, clockwise/counterclockwise rotation 1 in quick commissioning
Description
Macro drive unit
Assigning digital inputs to the commands:
Digital input 0: ON/OFF1 clockwise rotation
Digital input 1: ON/OFF1 counter-clockwise rotation
Default setting of the interfaces (Page 92)
Description
CO/BO: CU digital inputs, status
BI: ON/OFF (OFF1)
BI: Setpoint inversion
BI: 2/3 wire control command 1
BI: 2/3 wire control command 2
CO/BO: 2/3 wire control control word
2/3 wire control selection
1: Two-wire control, clockwise/counterclockwise rotation 1
Advanced commissioning
Factory setting
-
0
0
0
0
-
0
205