Siemens SINAMICS G120C Operating Instructions Manual page 362

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Advanced commissioning
8.34 Switchover between different settings
Selecting the number of drive data sets
You can use parameter p0180 to define the number of drive data sets (1 or 2).
Parameter
p0010 = 0
p0010 = 15
p0180
Copying the drive data sets
Parameter
p0819[0]
p0819[1]
p0819[2] = 1
Parameter
Parameter
p0010
r0051
p0180
p0819[0 ... 2]
p0820[C]
p0821[C]
p0826[M]
360
Description
Drive commissioning parameter filter
CO/BO: Drive data set DDS effective
Number of Drive Data Sets (DDS)
Copy drive data set DDS
BI: Drive data set DDS selection, bit 0
BI: Drive data set DDS selection, bit 1
Motor changeover, motor number
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Description
Drive commissioning: Ready
Drive commissioning: Data sets
Number of Drive Data Sets (DDS)
Description
Source drive data set
Target drive data set
Starts the copy operation
Factory setting
1
-
1
0
0
0
0
SINAMICS G120C Converters