Corrective maintenance
10.2 Downloading the converter settings
6. Back up the settings so that they are protected against power failure.
7. Start to commission the safety functions.
8. Enter the password for the safety functions.
9. Confirm the setting of the safety functions.
10.Exit commissioning of the safety functions.
11.Back up the settings so that they are protected against power failure.
12.Switch off the converter power supply.
13.Wait until all LEDs on the converter are dark.
14.Switch on the converter power supply again.
15.Perform a reduced acceptance test.
You have transferred the settings to the converter.
10.2.2.4

Download from IOP-2 operator panel

Overview
You can transfer the converter settings that are backed up on the IOP-2 operator panel back into
the converter.
394
Reduced acceptance after component replacement and firmware change (Page 417)
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK