Harmonic Currents; Emc Limit Values In South Korea; Protecting Persons From Electromagnetic Fields - Siemens SINAMICS G120C Operating Instructions Manual

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

11.9.1

Harmonic currents

Table 11-14
Harmonic number
Harmonic [%] for FSAA ... FSC referred to
the LO input current for U
Harmonic [%] for FSD ... FSF referred to
the LO input current
11.9.2

EMC limit values in South Korea

The EMC limit values to be observed for Korea correspond to the limit values of the EMC
product standard for variable-speed electric drives EN 61800-3 of category C2 or the limit
value class A, Group 1 to KN11.
By implementing appropriate additional measures, the limit values according to category C2
or limit value class A, Group 1, are observed.
Additional measures, such as the use of an additional RFI suppression filter (EMC filter), may
be necessary.
In addition, measures for EMC-compliant configuration of the plant or system are described
in detail in this manual.
You can find additional information about EMC-compliant configuration of the plant or
system on the Internet:
60612658)
The final statement on compliance with the applicable standard is given by the respective
label attached to the individual device.
11.10

Protecting persons from electromagnetic fields

Overview
Protection of workers from electromagnetic fields is specified in the European EMF Directive
2013/35/EU. This directive is implemented in national law in the European Economic Area (EEA).
Employers are obligated to design workplaces in such a way that workers are protected from
impermissibly strong electromagnetic fields.
To this end, assessments and/or measurements must be performed for workplaces.
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Typical harmonic currents as a % referred to the LO input current for U
= 1 %
K
EMC installation guideline
11.10 Protecting persons from electromagnetic fields
5th
7th
11th
54
39
11
37
21
7
(http://support.automation.siemens.com/WW/view/en/
Technical data
1%
K
13th
17th
19th
23rd
5.5
5
3
2
5
4
3
3
25th
2
2
439