8.15 Selecting physical units
Unit group
Parameters involved with p0595 belong to unit group 9_1.
The values that can be set and the technological units are shown in p0595.
Special features
You must optimize the technology controller after changing p0595 or p0596.
8.15.4

Setting the system of units and technology unit

Setting using Startdrive
Requirement
You are offline with Startdrive.
Procedure
1. In the project, select "Parameter".
2. Select "Units".
3. Select the system of units.
4. Select the technological unit of the technology controller.
5. Save your settings.
6. Go online.
The converter signals that offline, other units and process variables are set than in the
converter itself.
7. Accept these settings in the converter.
You have selected the motor standard and system of units.
254