9.2
Identification & maintenance data (I&M)
I&M data
The converter supports the following identification and maintenance (I&M) data.
I&M data Format
I&M0
u8[64] PROFIBUS
u8[54] PROFINET
I&M1
Visible String [32]
Visible String [22]
I&M2
Visible String [16]
I&M3
Visible String [54]
I&M4
Octet String[54]
When requested, the converter transfers its I&M data to a higher-level control or to a PC/PG
with installed STEP 7 or TIA Portal.
I&M0
Designation
Manufacturer-specific
MANUFACTURER_ID
ORDER_ID
SERIAL_NUMBER
HARDWARE_REVISION
SOFTWARE_REVISION
REVISION_COUNTER
PROFILE_ID
PROFILE_SPECIFIC_TYPE
IM_VERSION
IM_SUPPORTED
SINAMICS G120C Converters
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK
Explanation
Converter-specific data, read only
Plant/system identifier
Location code
Date
Any comment
Check signature to track changes for Safe‐
ty Integrated.
This value can be changed by the user.
The test signature is reset to the value
generated by the machine if p8805 = 0 is
used.
Format
Example for the con‐
tent
u8[10]
00 ... 00 hex
u16
42d hex (=Siemens)
Visible String [20]
"6SL3246-0BA22-1FA0"
Visible String [16]
"T-R32015957"
u16
0001 hex
char, u8[3]
"V" 04.70.19
u16
0000 hex
u16
3A00 hex
u16
0000 hex
u8[2]
01.02
bit[16]
001E hex
Alarms, faults and system messages
9.2 Identification & maintenance data (I&M)
Associated param‐
eters
-
p8806[0 ... 31]
p8806[32 ... 53]
p8807[0 ... 15]
p8808[0 ... 53]
p8809[0 ... 53]
Valid for PROFI‐
NET
---
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
Example for the
content
See below
"ak12-ne.bo2=fu1"
"sc2+or45"
"2013-01-21 16:15"
-
Values of r9781[0]
and r9782[0]
Valid for PROFI‐
BUS
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
✓
365