Siemens SINAMICS G120C Operating Instructions Manual page 378

Low voltage converters
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Alarms, faults and system messages
9.5 List of alarms and faults
Number
Cause
A07991
Motor data identification activa‐
ted
F08501
Setpoint timeout
F08502
Monitoring time, sign-of-life ex‐
pired
F08510
Send configuration data not valid •
A08511
Receive configuration data not
valid
A08526
No cyclic connection
A08565
Consistency error affecting adjust‐
able parameters
F13100
Know-how protection: Copy pro‐
tection error
F13101
Know-how protection: Copy pro‐
tection cannot be activated
F30001
Overcurrent
F30002
DC-link voltage overvoltage
376
Remedy
Switch on the motor and identify the motor data.
Check the PROFINET connection.
Set the controller to RUN mode.
If the error occurs repeatedly, check the monitoring time set (p2044).
Check the PROFINET connection.
Check the PROFINET configuration
Activate the control with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
The know-how protection and the copy protection for the memory card are
active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the converter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.
Check the following:
Motor data, if required, carry out commissioning
Motor connection method (Υ / Δ)
U/f operation: Assignment of rated currents of motor and Power Module
Line quality
Make sure that the line commutating reactor is connected properly
Power cable connections
Power cables for short-circuit or ground fault
Power cable length
Line phases
If this doesn't help:
U/f operation: Increase the acceleration ramp
Reduce the load
Replace the power unit
Increase the ramp-down time (p1121).
Set the rounding times (p1130, p1136).
Activate the DC-link voltage controller (p1240, p1280).
Check the line voltage (p0210).
Check the line phases.
Operating Instructions, 02/2023, FW V4.7 SP14, A5E34263257B AK