4. Settings

4-2-1. D/A converter

The D/A converter allows for analog output that corresponds
to the unit indicator value.
The D/A output circuit is isolated from the main unit circuit.
The analog output range is either 0–±10V voltage output or
4–20mA current output. Set the maximum voltage output
between ±1 V and ±10 V in 1V steps using the D/A max. volt-
age setting.
Analog output from zero (0 V, 4 mA) to full scale (±10 V, 20 mA)
can be achieved according to the digital values set using D/A
Zero and D/A full scale settings.
The zero point and full scale cannot be changed separately for
current output and voltage output.
D/A output is synchronized to the sampling frequency.
The following are examples of when "D/A MAX. VOLTAGE" is
set to 10V.
Setting example 1
D/A Zero
D/A full scale
Indicator value
100.00
0.00
−100.00
Setting example 2
D/A Zero
D/A full scale
Indicator value
120.00
20.00
−80.00
30
000.00
100.00
D/A output
10V(20mA)
0V(4mA)
−10V(--mA)
020.00
100.00
D/A output
10V(20mA)
0V(4mA)
−10V(--mA)
Setting example 3
D/A Zero
D/A full scale
Indicator value
120.00
20.00
−80.00
Setting example 4
D/A Zero
D/A full scale
Indicator value
10.00
−10.00
−30.00
ATTENTION
If calibration is conducted, when the rated capacity is con-
firmed, it will be set as the D/A full scale value.
020.00
−100.00
D/A output
−10V(--mA)
0V(4mA)
10V(20mA)
−010.00
020.00
D/A output
10V(20mA)
0V(4mA)
−10V(--mA)