Example For A 12-Pin Connection - Pilz PSEN sc L 3.0 08-12 Series Operating Manual

Hide thumbs Also See for PSEN sc L 3.0 08-12 Series:
Table of Contents

Advertisement

First commissioning
18. Switch the display in the work window to a live image by clicking on
Check the safety function of the safety laser scanner as indicated in
Inspection [
Each time the test piece enters into the safety zone, the OSSDs must switch to the OFF
state and the status of the OSSDs in the Monitoring work window must show the viola-
tion of the safety zone.
The OSSDs must switch to the OFF state each time the reference point changes bey-
ond the tolerance range, and the status of the OSSDs in the Monitoring work window
must show the changing of the reference points.
19. Select Download configuration to device, to transfer the configuration to the device.
Click Accept to activate the downloaded configuration in the connected device and re-
ject the existing configuration on the connected device.
Save the report in PDF format.
Click Reject to reject the downloaded configuration in the connected device and con-
tinue to use the existing configuration on the connected device. The downloaded con-
figuration in the connected device will be deleted.
10.3.2

Example for a 12-pin connection

Settings in the PSENscan Configurator for a safety laser scanner with 12‑pin connection:
Vertical application with reference contour monitoring, 1 zone set, 1 warning, manual re-
start, manipulation protection is active
Prerequisites
}
The safety laser scanner is already connected to the 12-pin male connector.
Procedure:
1. From the start page, select Create new configuration.
The Device selection window is displayed with a tab for Online and Overview of all
types.
2. Select the connected device from Overview of all types. Double-click the device.
The device is displayed in the work window and it can be configured.
3. Under Application, select the application VERTICAL and 12-pin connection.
Configuration
You can enter a title for the configuration under Name Configuration.
You can enter the name of the person who created the configuration under Author.
You can describe the configuration in detail under Description.
The Configurator Version is entered by the system and cannot be changed.
The Check sum is entered by the system and cannot be changed.
The Creation date is entered by the system and cannot be changed.
Operating Manual PSEN sc L 3.0/5.5 08-12
1005056-EN-06
95].
.