Warnings; Information - Pilz PSEN sc L 3.0 08-12 Series Operating Manual

Hide thumbs Also See for PSEN sc L 3.0 08-12 Series:
Table of Contents

Advertisement

Operation
11.3.2

Warnings

Message in the display
Icon
Text
BOOTF
INTF6
EXTTEMP
OVERTEMP
HIGH REFL-
BKG
11.3.3

Information

Message in the display
Icon
Text
ANTITAM-
PERING
BKP DONE
BKP IN PRO-
GRESS
CFG NO
MATCHING
Operating Manual PSEN sc L 3.0/5.5 08-12
1005056-EN-06
Error/cause
An error has occurred when starting
the system.
An error occurred during the system
test.
The ambient temperature is outside
the temperature range indicated in
the Technical details.
The temperature of the safety laser
scanner is outside the permitted
temperature range.
The reflection of the background is
too strong.
Error/cause
The wave function is activated.
Protection against
manipulation [
29]
has been ac-
tivated.
The backup copy of a configuration
was completed successfully.
The backup copy of a configuration
is created.
The configuration stored in the
safety laser scanner does not match
the configuration in the memory
module.
Description/measure
Perform a
reset of the safety laser
scanner [
107].
If the error persists, please contact
Pilz.
Perform a
reset of the safety laser
scanner [
107].
If the error persists, please contact
Pilz.
Ensure that the ambient temperature
is in the temperature range specified
in the
Technical details [
Ensure that the temperature of the
safety laser scanner is within the
temperature range specified in the
Technical details [
121].
Reduce the background reflection or
increase the safety distance (see
Distance to intense light sources and
to reflective surfaces [
Description/measure
The symbol flashes. Select the
safety laser scanner in PSENscan
Configurator and configure it.
Wait until the backup copy was cre-
ated successfully.
Follow the instructions in
configuration [
106].
121].
49]).
Restore
| 101