Project configuration
6.4

Monitoring of reference outlines

An outline within the area covered by laser beams can be defined and monitored in
PSENscan Configurator as a reference outline.
The outline must be outside the safety zone and it consists of at least 3 and a max. of 15
reference points.
When PSEN sc L 3.0/5.5 08-12 series detects a change of the outline, the safety laser
scanner switches the OSSDs to the OFF state. A change in the area of a tolerance that can
be set in PSENscan Configurator is accepted.
For vertical applications, national and international standards recommend monitoring a ref-
erence outline.
The reference outline is configured during the first installation of PSEN sc L 3.0/5.5 08-12
series. The distances measured during configuration are used as reference values for mon-
itoring the reference outline.