Mitsubishi Electric L26CPU-BT User Manual page 31

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

(2) Remote net ver.2 mode, remote net additional mode
A total of 64 device stations can be connected to a single master station.
However, the following conditions must all be satisfied.
{(a + a2 + a4 + a8)
+ (b + b2 + b4 + b8)  2
Condition 1
+ (c + c2 + c4 + c8)  3
+ (d + d2 + d4 + d8)  4}  64
[{(a  32) + (a2  32) + (a4  64) + (a8  128)}
+ {(b  64) + (b2  96) + (b4  192) + (b8  384)}
Condition 2
+ {(c  96) + (c2  160) + (c4  320) + (c8  640)}
+ {(d  128) + (d2  224) + (d4  448) + (d8  896)}]  8192
[{(a  4) + (a2  8) + (a4  16) + (a8  32)}
+ {(b  8) + (b2  16) + (b4  32) + (b8  64)}
+ {(c  12) + (c2  24) + (c4  48) + (c8  96)}
Condition 3
+ {(d  16) + (d2  32) + (d4  64) + (d8  128)}]
 2048
{(16  A) + (54  B) + (88  C)}  2304
Condition 4
CHAPTER 3 SPECIFICATIONS
a: The total number of ver.1 compatible device stations that
occupy 1 station, and ver.2 compatible device
stations that occupy 1 station which are set to
"Single".
b: The total number of ver.1 compatible device stations that
occupy 2 stations, and ver.2 compatible device
stations that occupy 2 stations which are set to
"Single".
c: The total number of ver.1 compatible device stations that
occupy 3 stations, and ver.2 compatible device
stations that occupy 3 stations which are set to
"Single".
d: The total number of ver.1 compatible device stations that
occupy 4 stations, and ver.2 compatible device
stations that occupy 4 stations which are set to
"Single".
a2: The number of ver.2 compatible stations that occupy 1
station which are set to "Double".
b2: The number of ver.2 compatible stations that occupy 2
stations which are set to "Double".
c2: The number of ver.2 compatible stations that occupy 3
stations which are set to "Double".
d2: The number of ver.2 compatible stations that occupy 4
stations which are set to "Double".
a4: The number of ver.2 compatible stations that occupy 1
station which are set to "Quadruple".
b4: The number of ver.2 compatible stations that occupy 2
stations which are set to "Quadruple".
c4: The number of ver.2 compatible stations that occupy 3
stations which are set to "Quadruple".
d4: The number of ver.2 compatible stations that occupy 4
stations which are set to "Quadruple".
a8: The number of ver.2 compatible stations that occupy 1
station which are set to "Octuple".
b8: The number of ver.2 compatible stations that occupy 2
stations which are set to "Octuple".
c8: The number of ver.2 compatible stations that occupy 3
stations which are set to "Octuple".
d8: The number of ver.2 compatible stations that occupy 4
stations which are set to "Octuple".
A: Number of remote I/O stations  64
B: Number of remote device stations  42
C: Number of local stations, standby master stations and
intelligent device stations  26
3
29