Mitsubishi Electric L26CPU-BT User Manual page 228

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

(1) Functions
(a) Operation chart for the G(P).RLPASET instruction.
Programmable controller CPU
Command
Device
memory
4)
1)
Pass the network parameters set in (S1) to (S5) to the master module specified by Un.
2)
The master module analyzes the settings of the network parameters.
3)
If the network parameter settings are correct, the data link is started.
4)
The device specified by (D) turns on.
(b) It is only possible to execute one G(P).RLPASET instruction at a time.
(c) There are two types or interlock signals for the G(P).RLPASET instruction: the
completion device (D) and status display device at completion (D) + 1.
• Completion device
Turns ON in the END Processing of the scan where the G(P).RLPASET instruction is completed, and turns
OFF in the next END processing.
• Status display device at completion
Turns On and OFF depending on the completion status of the G(P).RLPASET instruction.
Normal completion: Stays OFF and does not change.
Abnormal completion: Turns ON in the END processing of the scan where the G(P).RLPASET instruction
is completed, and turns OFF in the next END processing.
226
G(P).RLPASET
1)
Execution result
Master module
Network
parameter
2)
3) Data link start