Mitsubishi Electric L26CPU-BT User Manual page 149

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

(4) Setting method
Perform the setting using GX Works2.
(a) Setting the master station
Configure the settings in "Type" and "Standby Master Station No." of the network parameter as follows.
For other settings, refer to
1.
Open the "Network Parameter" window to configure the setting in "Type" as follows.
station goes down, the
Function
standby master station
operates as a master
station to continue data
Master station switching
function
Master station duplex
function
Data link start function using
a standby master station
2.
Set the station number to 0 when "Master Station (Duplex Function)" is selected in "Type".
3.
Set "Standby Master Station No." from 1 to 64.
When "Master Station (Duplex Function)" is selected in "Type"
Page 77, Section 7.3.2
When the master
When a failed master
station becomes
normal again, it returns
as a standby master
link.
Operation
When only a standby
master station is
started up, it starts data
link as a master station.
station.
CHAPTER 8 FUNCTIONS
Setting in "Type"
Master Station
Master Station (Duplex
Function)
Master Station (Duplex
Function)
: Enabled, : Disabled
8
147