15.4.3

Status logging

This function logs the data link status of all stations. When multiple stations, such as stations of a specific station
number and higher, repeatedly fail and recover, the cause and location of the problem (e.g. poor cable contact or
noise) can be identified easily.
If "RAM + Flash ROM" is selected, the first 45 logs after starting logging are stored to the flash ROM. The logs stored
to the flash ROM can be checked after turning off and on the power or after resetting the programmable controller
CPU.
(1) Operating procedure
1.
In GX Works2, select [Diagnostics] and then [CC-Link Diagnostics] and double-click the "Status
Logging" icon.
2.
Select the log storage area.
Select either of "RAM" or "RAM + Flash ROM".
If GX Works2 cannot be connected continuously, select "RAM + Flash ROM". The logs (max. 45) stored in
the flash ROM can be confirmed by connecting GX Works2 after the log collection.
If GX Works2 can be connected continuously, the maximum of 5000 logs can be collected for either
"RAM" or "RAM + Flash ROM".
380
Log display part