Error code
Error details
(hexadecimal)
Operation when CPU is
B392
down specified error
(parameter)
Scan mode specification
B393
error (parameter)
Number of automatic return
B394
stations setting error
(parameter)
B395
System error
Station number overlap
B396
error
(parameter)
Station information setting
B397
error
(parameter)
Number of occupied
B398
stations setting error
(parameter)
Number of connected
B399
modules setting error
(parameter)
Standby master station
B39A
specification error
(loading status)
Reserved station
B39B
specification error
Standby master station
B39C
setting error
Reserved station 0 points
B39D
setting error
8/16-point remote I/O
B39E
station setting error
Remote net additional mode
B39F
station number invalid
366
Cause of error occurrence (details)
The operation when the CPU is down
specification parameter was set to a value
other than "0 or 1".
The scan mode parameter was set to a value
other than "0 or 1".
The number of automatic return stations
parameter was set to a value other than "1 to
10".
A duplicate station number was specified
with the station information parameter.
The station information parameter setting
does not meet the following condition:
(16A) + (54B) + (88C)  2304
A: Number of remote I/O stations
B: Number of remote device stations
C: Number of intelligent device stations
(including local stations)
The number of occupied stations in the
station information parameter was set to a
value other than "1 to 4".
The number of connected modules
parameter was set to a value other than "1 to
64".
The station number of the standby master
station differs from that set in the "Standby
Master Station No." network parameter of the
master station, or the station set in the
"Standby Master Station No." network
parameter of the master station is a local
station.
All stations were set as reserved stations.
Any other than Intelligent device station has
been set to the station type for the "Standby
Master Station No." specified in the master
station network parameter.
The mode setting is different between the
master and standby master stations.
Reserved station 0 points setting has been
made in the remote net additional mode.
Reserved station 0 points setting has been
made for the station that is not a reserved
station.
Remote I/O station points setting is 8/16
points in the remote net additional mode.
8/16 points setting has been made for the
station other than the remote I/O station.
Make 8/16 points setting for the same remote
I/O station.
In the remote net additional mode, the
"maximum station number of ver.1
compatible device stations" is greater than
the "minimum station number of ver.2
compatible device stations" in the network
parameter setting.
Corrective action
Set "0 or 1".
Set "0 or 1".
Set a value within the range from "1
to 10".
Please consult your local Mitsubishi
representative.
Set so that station numbers are not
duplicated.
Set the parameter so that it meets
the condition shown on left.
Set a value within the range from "1
to 4".
Set a value within the range from "1
to 64".
Change the parameter setting of the
master station, or change the station
number setting of the local/standby
master station, and then reset the
CPU module of the local/standby
master station.
Check the reserved station
specification.
Specify the standby master station
as an intelligent device station.
Make the same setting to the master
and standby master stations.
Change the mode to the remote net
ver.2 mode.
Set the station of reserved 0 points
setting as a reserved station.
Change the mode to the remote net
ver.2 mode.
8 points setting and 16 points setting
have been made for the same
remote I/O station.
Make either 8 points setting or 16
points setting for the remote I/O
station.
In the remote net additional mode,
make network parameter setting so
that the "maximum station number of
ver.1 compatible device stations" is
less than the "minimum station
number of ver.2 compatible device
stations".
Detectability
Master
Local
station
station