Mitsubishi Electric L26CPU-BT User Manual page 415

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

Number
Name
SB0065
Input data status of host
(5E6
, b5)
data link faulty station
H
SB0066
(5E6
, b6)
H
Number of host occupied
stations
SB0067
(5E6
, b7)
H
SB006A
Switch setting status
(5E6
, b10)
H
SB006D
Parameter setting status
(5E6
, b13)
H
SB006E
Host station operation
(5E6
, b14)
status
H
Setting status of block
SB006F
guarantee of cyclic data
(5E6
, b15)
H
per station
SB0070
Master station information
(5E7
, b0)
H
SB0071
Standby master station
(5E7
, b1)
information
H
SB0072
Scan mode setting
(5E7
, b2)
information
H
SB0073
Operation specification
(5E7
, b3)
when CPU is down status
H
SB0074
Reserved station specified
(5E7
, b4)
status
H
SB0075
Error invalid station
(5E7
, b5)
specified status
H
Description
Indicates the status of the data link faulty station setting configured
for the host station.
OFF: Clear
ON: Retain
Indicates the setting status of host occupied stations.
Number of occupied
SB0066
station
1 station
OFF
2 stations
OFF
3 stations
ON
4 stations
ON
Indicates the switch setting status.
OFF: Normal
ON: Setting error exists (the error code is stored in SW006A)
Indicates the parameter setting status.
OFF: Normal
ON: Setting error exists (the error code is stored in SW0068)
Indicates the data link communication status with other stations.
OFF: Being executed
ON: Not executed
Indicates the "Block Data Assurance per Station" setting status.
OFF: Not set
ON: Set
Indicates the data link status.
OFF: Data link control by the master station
ON: Data link control by the standby master station
Indicates whether or not a standby master station is present.
OFF: Not present
ON: Present
Indicates the scan mode setting information.
OFF: Asynchronous mode
ON: Synchronous mode
Indicates the operation specification status using a parameter
when the CPU is down.
OFF: Stop
ON: Continue
Indicates the reserved station specification status using a
parameter.
OFF: No specification
ON: Specification exists (information is stored in SW0074 to
SW0077)
Depending on the link refresh timing, SB0074 may be updated with
the time difference of one sequence scan from the update of the
reserved station specified status (SW0074 to SW0077).
Indicates the error invalid station specification status using a
parameter.
OFF: No specification
ON: Specification exists (information is stored in SW0078 to
SW007B)
Depending on the link refresh timing, SB0075 may be updated with
the time difference of one sequence scan from the update of the
error invalid station specified status (SW0078 to SW007B).
Availability
(: Available, : Not available)
Online
Master
Local
station
station
SB0067
OFF
ON
ON
OFF
*4
APPENDICES
A
Offline
413