Mitsubishi Electric L26CPU-BT User Manual page 332

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

(2) Operation Setting in PLC Parameter
Select "PLC Parameter" - "Operation Setting", and set as follows.
There are two directions for the link special relay/register (SB/SW) of the head module: the writing direction and
the reading direction.
1) When writing to link special relay/register (SB/SW), set the following transfer destination.
• Link special relay: SB1000 to SB100F
• Link special register: SW1000 to SW100F
2) When reading from link special relay/register (SB/SW), set the following transfer origin.
• Link special relay: SB1040 to SB11FF
• Link special register: SW1040 to SW11FF
The setting example above shows the following transfer.
Link special relay/register (SB/SW)
(a) Precautions
Do not include the following CC-Link special relay/register (SB/SW) in the setting range for inter-device
transfer.
• Link special relay: SB0010 to SB003F
• Link special register: SW0010 to SW003F
330
Head module side
SB1000 to SB100F
SW1000 to SW100F
SB1040 to SB11FF
SW1040 to SW11FF
Direction
Link special relay/register (SB/SW)
CC-Link side
SB0000 to SB000F
SW0000 to SW000F
SB0040 to SB01FF
SW0040 to SW01FF