Loop Test 1 - Mitsubishi Electric L26CPU-BT User Manual

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

6.5.1

Loop test 1

Loop test 1 checks the connection status and the status of communication with device stations.
Perform the loop test 1 according to the following procedure.
68
Start
Check the following befor executing loop test 1:
The programmable controller CPU switch
is set to "STOP".
Set the following items at the network
parameter in GX Works2.
Type
: Master Station or
Master Station(Duplex Function)
Station No.
: 0
Mode
: Loop Test
Transmission
: 156kbps to 10Mbps
Speed
(Must be the same as the one
used in system operation.)
Do not change other network parameters.
Write the network parameters set by GX Works2
to the programmable controller CPU.
To the next figure
RUN/STOP/
RESET switch