Heating, Air Conditioner - Edition 06.2000
Ambient temperature-dependent resistance of temperature sensors/senders in kω(kilo-ohms)
At sensor/sender installation location, temperature measured in °C
70
Test step 3
Fresh air blower -V2 and relevant control unit -J216
Protected by copyright. Copying for private or commercial purposes, in part or in whole, is not
permitted unless authorised by AUDI AG. AUDI AG does not guarantee or accept any liability
with respect to the correctness of information in this document. Copyright by AUDI AG.
Select measuring range on hand-held multimeter V.A.G 1526:
Voltage measurement (20V =)
- Adapter cable V.A.G 1598/11 connected
Test step
V.A.G 1598
socket
3.1
16
and
earth
3.2
4
and
earth
Note:
Earth applied e.g. to connector D contact 14.
64
01 - Self-diagnosis, Electrical check
(degrees Celsius)
-30
-20
-10
0
5
10
15
20
25
30
35
40
50
60
Testing of
▪ Test conditions
- Additional opera‐
tions
Control unit -J126
▪ Ignition on.
Power supply for
▪ Ignition on.
fresh air blower -V2
Sender
Temperature sensor
-G192
-G17
-G89
(52.7)
18.1
(28.6)
9.95
16.2
5.59
9.40
3.28
7.27
2.54
5.66
1.99
4.45
1.57
3.50
1.25
2.79
1.00
2.23
0.80
1.80
0.65
1.45
0.53
0.97
0.36
0.67
0.25
0.47
-
Specified value
Remedies if speci‐
- Voltage less than 5
- Use current flow di‐
V.
agram to locate and
Fresh air blower not
eliminate short to
running.
positive in the wiring
between -J126 and -
E87.
Replace control unit
-J126.
- approx. battery
- Use current flow di‐
voltage
agram to repair pow‐
er supply.
Sender
-G191
-
-
(47)
(29)
(23)
18.5
15
12.2
10.0
8.3
6.8
5.7
4.1
2.9
2.2
fied value not at‐
tained