Parameter
Power frequency
Power-supply voltage magnitude 95 % of the measurement should be
Voltage unbalance
Subgroup Total Harmonic Distor-
tion (THDS)
Supply voltage interruptions
Harmonic voltages
Mains signaling voltages
Start and Stop of Recorders
8.6.9
Table 8-21
Parameter
Start record option
Start time
Recording status
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and 2-wire connections.
61
62
The frequency "YYY" and limit "xxx" are based on the configured frequency.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
99.5 % of the measurement should be
within a deviation of -1.0 % to 1.0 %
100 % of the measurement should be
within a deviation of -6.0 % to 4.0 %
within a deviation of -10.0 % to 10.0 %
100 % of the measurement should be
within a deviation of -15.0 % to 10.0 %
61
95 % of the measurement should be less
than 2.0 %
100 % of the measurement should be less
than 3.0 %
95 % of measurement should be less than
8.0 %
1. Short interruption until 1 second dura-
tion
2. Short interruption until 3 minute dura-
tion
3. Long interruption longer than 3 minute
duration
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
62
Supply voltage should be in -15.0 % to
+15.0 % deviation of the nominal/
declared supply voltage
99.0 % of "YYY" Hz mains signaling
voltage should be less than "xxx" % of the
nominal/declared supply voltage
Settings for Start and Stop of Recorders
Default Setting
Start next 10th minute
–
–
Operational Indications and Operating Parameters
8.6 Recording and Reporting
Setting Range
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Any setting for user-defined
evaluation mode
Setting Range
Start next minute
Start next 10th minute
Start immediately
Start next hour
Start next day
Display of the start time in:
Depends on the configuration of date/
time format.
Not settable
Status display of recorder started or
recorder stopped