Technical Data
7.2 Test Data
High frequency electromagnetic field, ampli-
tude‑modulated
Class III, IEC 61000-4-3
Fast transient bursts
Class III, IEC 61000-4-4
High energy surge voltages (SURGE),
Installation class III
IEC 61000-4-5
Auxiliary voltage
Measuring inputs, binary inputs, and relay outputs
Line-conducted high frequencies, amplitude-modu-
lated,
Class III , IEC 61000-4-6
Power system frequency magnetic field
IEC 61000-4-8, Class IV
1 MHz test
Class III, IEC 61000-4-18
EMC Test for Noise Emission (Type Test)
Standard
Disturbance voltage to lines, only auxiliary voltage
IEC-CISPR 22
Disturbance-field strength IEC-CISPR 22
7.2.3

Mechanical Stress Tests

Vibration and Shock Stress during Stationary Operation
Standards
Vibration
IEC 60068-2-6 test Fc
342
10 V/m
80 MHz to 3 GHz
80 % AM
1 kHz
2 kV; 5 ns/50 ns
5 kHz Burst length = 15 ms
Repetition rate 300 ms
Both polarities
R
= 50 Ω
i
Test duration 1 min
Impulse: 1.2 μs/50 μs
Common mode: 2 kV; 12 Ω; 9 μF
Diff. mode:1 kV; 2 Ω; 18 μF
Common mode: 2 kV; 42 Ω; 0.5 μF
Diff. mode: 1 kV; 42 Ω; 0.5 μF
10 V (150 kHz to 80 MHz); 80 % AM (1 kHz)
30 A/m continuous; 300 A/m for 3 s
2.5 kV (peak); 1MHz; τ = 15 μs
400 Surges per s
Test duration 1 min; R
= 200 Ω
i
IEC EN 61000-6-4
150 kHz to 30 MHz Limit Class A
30 MHz to 1 GHz Limit Class A
IEC 60068
Sinusoidal 10 Hz to 60 Hz: ±0.075 mm amplitude;
60 Hz to 150 Hz: 1 g acceleration
Frequency sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
SICAM, SICAM Q100 7KG95xx, Manual