Co2 Emissions; Function Description; Configuration And Evaluation Via User Interface - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

[sc_q100_frozen energy, 1, en_US]
Figure 2-83

CO2 Emissions

2.4.6
2.4.6.1

Function Description

The device supports to calculate and show the CO
imported and exported active energy, and the configured CO
same as the configured freeze energy interval. The calculated CO
Modbus registers. For the register number, refer to the SICAM Q100 system manual.
If you change the parameters of Voltage transformer or the parameters of Current transformer in Configure
→ Operational parameters → Process connections → AC measurement, the calculated CO
values are reset to 0.
2.4.6.2

Configuration and Evaluation via User Interface

Parameterization
To change the settings of the CO
In the navigation window, click Energy management → CO
[sc_q100_CO2 emissions, 1, en_US]
Figure 2-84
Configure the respective parameters according to the following table.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Value View and Evaluation Tab for Frozen Energy
emissions in the Configure tab, proceed as follows:
2
Configure Tab, CO
Emission
2
emissions. The calculation is based on the accumulated
2
emission factor. The calculation interval is the
2
emission values are transmitted by the
2
emissions.
2
Device Functions
2.4 Energy Management
emission
2
117

Advertisement

Table of Contents
loading

Table of Contents