[sc_q100_recorder parameters_measurement, 1, en_US]
Figure 2-90
NOTE
i
i
The voltage is recorded in the following network types:
3P4W (3 phases/4 wires): phase-to-phase voltage or phase-to-ground voltage
3P3W (3 phases/3 wires): only phase-to-phase voltage
Configure the respective parameters according to the following table.
Table 2-39
Parameter
Measurement recorder
Average intervals - Frequency
Short term flicker
Long term flicker
Average interval - Voltage /
Unbalance / Harmonics
Record additional data (I, P, Q,
S etc.)
Recorder of average - Min
Recorder of average - Max
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Configure Tab, Recorder Parameters Input/Output Window
Settings for Recorder Parameters
Default Setting
10 s
10 min
2 h
10 min
no
no
no
2.5 Device-Recorder Functions
Setting Range
fixed
fixed
fixed
30 s
1 min
10 min
15 min
30 min
1 h
2 h
no
yes
no
yes
no
yes
Device Functions
125