Device Functions
2.2 Setting Process Connections and Other Settings
[sc_q100_ac_measurement, 1, en_US]
Figure 2-1
Configure the respective parameters according to the following table.
NOTE
i
i
When configuring values ensure that they do not contradict each other.
Table 2-9
Parameter
Rated frequency
5
Network type
Power quality values for
In the case of contradictory parameter settings, Primary rated voltage is indicated as faulty (red) and Network type as not adjust-
5
able (gray). Moreover, the Send button is disabled.
6
This parameter is available only when the network type is 4-wire, 3-phase, unbalanced.
44
Configure Tab, AC Measurement, Basic Settings
Settings for AC Measurement
Default Setting
50 Hz
4-wire, 3-phase, unbal-
anced
Phase to neutral
6
Setting Range
Setting 50 Hz: 50 Hz ± 7.5 Hz
Setting 60 Hz: 60 Hz ± 9 Hz
1-phase network
3-wire, 3-phase balanced
3-wire, 3-phase, unbalanced (2 * I)
3-wire, 3-phase, unbalanced (3 * I)
4-wire, 3-phase, balanced
4-wire, 3-phase, unbalanced
Phase to neutral
Phase to phase
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020