Configuration And Evaluation Via Display - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Parameter
Source Type Energy Counter
Energy counter
Energy increase per pulse
Output time for pulse operating
mode
After the parameterization, click Send.
In the navigation window, select Finish configuration and click Activation.
Behavior when Activating the Set of Parameters after the Set of Parameters was Changed
Persistent: The binary output is set to the new status (ON or OFF) as defined by the current indication.
Pulse: If the binary output is ON in pulse mode while activating the parameter set, the binary output is imme-
diately switched to OFF after the parameter set has been activated. This happens even if the parameterized
Output time for pulse operating mode has not yet elapsed.
Evaluation
To display the binary output values in the Value view and evaluation tab, proceed as follows:
In the navigation window, select Operational parameters → Process connections and click Binary
status.
[sc_q100_BO_evaluation, 1, en_US]
Figure 2-11
Depending on the parameterized source type, the indications routed to the binary outputs and energy coun-
ters are evaluated.
2.2.4.3

Configuration and Evaluation via Display

Submenu Binary Outputs
[dw_submenu_binary_inputs_outputs, 1, en_US]
Figure 2-12
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
-none-
14
1.00 Wh
20 * 10 ms = 200 ms
Evaluation Binary Status (Binary Outputs)
Configuration and Evaluation Binary Outputs
2.2 Setting Process Connections and Other Settings
Setting Range
Acc. to list box
0.10 Wh/VAh/varh to
1 000 000.00 Wh/VAh/varh
50 ms to 3 600 000 ms
Device Functions
53