Device Functions
2.7 Ethernet Communication
Parameter
Keep alive time
Communication supervision
time
NOTE
i
i
The 3 port numbers must be different from each other.
•
After the parameterization, click Send.
•
In the navigation window, select Finish configuration and click Activation.
Number of Connections (not configurable)
Up to 5 TCP connections are possible:
•
Without user-defined port 1: 4 connections via the standard port 502
•
With user-defined port 1: 2 connections via the standard pot 502 and 2 connections via the configured
port number
•
With user-defined port 2: 1 connection via the configured port number
2.7.2.2
Configuration via Display
Submenu Modbus TCP Settings
The operation is carried out with the softkeys F1 to F4.
[dw_q100_display_communication_Modbus_TCP, 1, en_US]
Figure 2-114
2.7.2.3
Diagnosis Modbus TCP
The diagnosis for Modbus TCP allows analyzing parameters and communication as well as resetting the diag-
nostic counters.
NOTE
i
i
The diagnostic data of Modbus TCP are displayed only if the bus protocol has been selected in the tab
Configure → Administrative → Ethernet communication.
If the protocol has not been selected, the Diagnosis Modbus TCP window displays -none-.
For the diagnosis of the protocol Modbus TCP in the Maintenance tab, proceed as follows:
•
In the navigation window, select Diagnosis and click Modbus.
The Modbus window opens and the Modbus TCP protocol is displayed. For Modbus TCP the Standard
server, the User-port server and the Connection data are analyzed.
156
Default Setting
10 s
600 (* 100 ms)
Submenu Communication via Modbus TCP
Setting Range
0 s = switch off
1 s to 65 535 s
0 s = none
100 ms to 6 553 400 ms
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020