Parameter
Software filtering time
(only settable if Routed as: is
set to Status information)
Source inverted
Add entry to operational log
(only settable if Routed as: is
set to Status information)
Binary input indication
•
After the parameterization, click Send.
•
In the navigation window, select Finish configuration and click Activation.
Evaluation
To display the binary input values in the Value view and evaluation tab, proceed as follows:
•
In the navigation window, select Operational parameters → Process connections and click Binary
status.
[sc_q100_BI_evaluation, 1, en_US]
Figure 2-4
Depending on the parameterization, either the status information or the source is evaluated.
2.2.3.3
Configuration and Evaluation via Display
Submenu Binary Inputs
[dw_submenu_binary_inputs_outputs, 1, en_US]
Figure 2-5
13
31 bytes of UTF-8
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
1 (* 2 ms)
no
yes
For example for terminal
U3/2:
Binary Input 2
Evaluation Binary Status (Binary Inputs)
Configuration and Evaluation of the Binary Inputs
2.2 Setting Process Connections and Other Settings
Setting Range
2 ms to 120 000 ms
(settable in 2-ms increments)
no
yes
no
yes
13
Max. 31 characters
Device Functions