Quick Start (P001 to P007)

P001 Operation
Sets the type of measurement required for the application.
Primary Index
Values
For DPD and DPA Programming
To set an AiRanger DPL Plus for DPA or DPD functions, Point 3 must be set to either 4 or
5 (as required). Points 1 and 2 cannot be set to 4 or 5, but these points are used to
calculate the value in point 3.
This table shows the available functions:
Operation [index]
P001 [1]
P001 [2]
P001 [3]
When DPD or DPA operation, Parameter values for P001 to P007 must be identical for
Points 1 and 2.
When DPD is selected, Point 3 = Point 1 - Point 2
When DPA is selected, Point 3 = (Point 1 + Point 2) / 2
When Tripper is selected, see Technical Reference Application Examples / Example
5 on page 107.
When Out-of-service is selected, the transducer is not scanned, alarm relay(s)
energize, pump relay(s) de-energize, and mA output(s) go to the Empty vessel value.
7ML19981BD02
Global
0
Out-of-service
1
Level – how full the vessel is (Point 1 and/or 2 only)
2
Space – how empty the vessel is (Point 1 and/or 2 only)
Distance – distance from transducer to material (Point 1 and/
3
*
or 2 only)
DPD – dual point difference (Point 3 only, Point 1 and 2 must
4
be Level)
DPA – dual point average (Point 3 only, Point 1 and 2 must be
5
Level)
Tripper – equipment position monitoring greater than 60 m
8
(200 ft.) (Point 1 only) (Select TRIP or SWITCH on circuit
board)
Available Values
1, 2, 3
1, 2, 3
4,5
AiRanger DPL Plus – INSTRUCTION MANUAL
Page 29