Device Functions
2.2 Setting Process Connections and Other Settings
NOTE
i
i
The following voltages must be in the same range:
•
Operating voltage
•
Primary rated voltage of the voltage transformer
•
Nominal/declared supply voltage
•
After the parameterization, click Send.
•
In the navigation window, select Finish configuration and click Activation.
2.2.2.2
Configuration via Display
Submenu Basic Parameters
[dw_q100_submenu_basic_settings, 1, en_US]
Figure 2-2
Table 2-10
Parameter
Voltage Inputs
Connection type
10
PQ values for
Use PTs?
10
This parameter is available only when the connection type is 3PW4.
46
Submenu, Basic Parameters
Basic Parameter Settings
Default Setting
3P4W
ph-n
No
(no checkmark)
Setting Range
1P2W (1-phase system)
3P3WB (3-wire, equal load)
3P3W_2I (3-wire, any load (2*I))
3P3W_3I (3-wire, any load (3*I))
3P4WB (4-wire, equal load)
3P4W (4-wire, any load)
ph-n
ph-ph
Yes (checkmark)
No (no checkmark)
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020