Siemens SICAM Q100 7KG95 Series Manual page 176

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

Device Functions
2.8 Serial Communication
[sc_Config Modbus slave devices, 1, en_US]
Figure 2-128
Configure the respective parameters according to the following table.
Table 2-63
Parameter
Name
Activated
Device address / Unit ID
(Modbus slave device address)
Scan cycle for measured values 50 (*10 ms)
Scan cycle for indications
Response timeout
Retry limit
176
Configure Tab, Modbus Slave Devices, Device 1 Activated
Settings for Modbus Slave Device 1
Default Setting
Modbus slave device 1
No
1
0 (*10 ms)
10 (*10 ms)
2
Setting Range
Max. 31 characters
No
Yes (= Activation of the option field):
The buttons for parameterization of the
mapping data are also activated for the slave
device here.
1 to 247
Address corresponds to the Unit ID in the
Modbus TCP telegram with simultaneous use of
the Modbus Gateway function
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = Each interrogation cycle
Minimum time difference between the meas-
ured-value requests
0 to 36 0000 * 10 ms
(10 ms to 1 h)
0 = Each interrogation cycle
Minimum time difference between the meas-
ured-value requests
1 to 6000 * 10 ms
(10 ms to 60 s)
0 to 10
(0 = No request retries)
Number of request retries after expiration of
Response timeout before a communication
error for the Modbus slave is identified.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020