Recording And Reporting; Event Recorders; Waveform Recorder And Trigger Management - Siemens SICAM Q100 7KG95 Series Manual

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100 7KG95 Series:
Table of Contents

Advertisement

8.6

Recording and Reporting

Event Recorders

8.6.1
Parameter
Voltage event
Swell threshold
Dip threshold
Interruption threshold
Event hysteresis
Event detection mode
RVC event
RVC threshold
58
RVC hysteresis
RVC event detection
59
mode
Frequency event
Underfrequency threshold 1 %
Overfrequency threshold
Voltage-unbalance event
Voltage-unbalance
threshold

Waveform Recorder and Trigger Management

8.6.2
Table 8-15
Parameter
Voltage trigger limits
Trigger active
Tolerance unit
Lower threshold
Upper threshold
Hysteresis
According to IEC 61000-4-30 Edition 3.0, RVC hysteresis is recommended to be half of the threshold.
58
59
RVC event detection mode will always be synchronized with the setting Event detection mode.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Default Setting
110 %
90 %
5 %
2 %
ph-N
6 %
3 %
ph-N
1 %
5 %
Settings for Trigger Management
Default Setting
Voltage event
Percentage
90.00 % of the nominal/declared supply
voltage
110.00 % of the nominal/declared
supply voltage
2.00 % of the nominal/declared supply
voltage
Operational Indications and Operating Parameters
8.6 Recording and Reporting
Setting Range
105 % to 140 %, increments of 5 %
75 % to 95 %, increments of 5 %
1 %, 2 %, 3 %, 5 %, 8 %, 10 %
1 % to 6 %, increments of 1 %
ph-N
ph-ph
1 % to 6 %, increments of 1 %
0.5 % to 3 %, increments of 0.5 %
ph-N
ph-ph
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
0.1 % to 1.0 %, increments of 0.1 %
1.0 % to 5.0 %, increments of 1.0 %
1 % to 5 %, increments of 1 %
Setting Range
No
User-defined
Voltage event
Percentage
Numerical
0.00 % to 99.99 % of the nominal/
declared supply voltage
0.0 V to 1 000 000.0 V
100.0 % to 10 000.0 % of the nominal/
declared supply voltage
0.0 V to 1 000 000.0 V
0.0 % to 50.0 % of the nominal/
declared supply voltage
359