Device Functions
2.3 Measurement and Evaluation Functions
Configure the respective parameters according to the following table.
Table 2-22
Parameter
Voltage Event
Swell threshold
Dip threshold
17
Interruption threshold
Hysteresis
Event detection mode
After parameterization click Send.
In the navigation window, select the Finish configuration menu and click Activation.
Evaluation
To display the Events values in the Value view and evaluation tab, proceed as follows:
In the navigation window, select Evaluation and data management and click Events.
The information of the latest 20 voltage events is shown without query.
According to the EN 50160 standard in the PQ report, the default setting of dip and swell (90 % and 110 %) is recommended.
17
18
Only for the 3P4W (3-phase/4-wire) unbalanced network type, you can select the ph-N or ph-ph option as event detection mode.
86
Settings for Voltage Events
Default Setting
110 %
17
90 %
5 %
2 %
18
ph-N
Setting Range
105 % to 140 %, increments of 5 %
75 % to 95 %, increments of 5 %
1 %, 2 %, 3 %, 5 %, 8 %, 10 %
1 % to 6 %, increments of 1 %
ph-N