Example: 3-Wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
[dw_3-wire-network-2x-current, 1, en_US]
Figure 4-12
NOTICE
The secondary voltage on terminal F (voltage) must not exceed AC 600 V (AC 347 V for UL).
Non-observance can cause material damage.
Make sure that the maximum permissible phase-to-ground voltage (PE) is not exceeded.
²
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Example: 3-Wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
Commissioning and First Steps
4.12 Connection Principle