Configure the respective parameters in the list boxes according to the following table.
If you update the percentage of any record type, the estimation data is changed with a certain ratio, and
vice versa.
Table 2-51
Parameter
Event recorder
Measurement recorder
Trend recorder
Fault recorder
Mains signaling voltage
recorder
After parameterization click Send.
In the navigation window, select the Finish configuration menu and click Activation.
NOTE
i
i
The total percentage of all record assignments keeps 100 %. If the input is invalid, a red color warning
appears and the Send button is disabled.
If the parameter of any record type exceeds the configurable range, the parameter percentage and
estimation are flagged in red, and the Send button is disabled.
If the percentage of free memory falls below 0 %, it is also flagged in red and the Send button is disa-
bled.
Storage Analysis
The Memory management shows the current Used ratio of the memory size for the individual recorders.
To display the Used ratio in the Value view and evaluation tab, proceed as follows:
In the navigation window, select Evaluation and data management and click Memory management.
SICAM, SICAM Q100 7KG95xx, Manual
E50417-H1040-C522-A8, Edition 09.2020
Settings for Memory Management
Default Setting
1.0 %
35.0 %
(The recording time depends on the
aggregation interval.)
47.0 %
(residual storage capacity)
3.0 %
(Numbers of records depends on the
fault-record time.)
14 %
(Numbers of records depends on the
record time of the mains signaling
voltage.)
Device Functions
2.5 Device-Recorder Functions
Setting Range
1 % to 19 %
33 % to 51 %
31 % to 49 %
3 % to 21 %
14 % to 20 %