Parameter assignment and addressing
8.2 QUICK START [01]
8.2

QUICK START [01]

 
 
01
AUTO INIT
 
02
MANUAL INIT
 
03
LEAKAGE TEST
 
04
SPEED TEST
 
05
OVERSHOOT
06
VALVE TYPE
1)
07
APPLICATION
2)
WIZ = wizard
visible if valve types have been stored at the factory.
1)
not visible if a valve type was selected for "VALVE TYPE" [06].
2)
44
Meaning
WIZ
Enables automatic initialization of the valve. The end positions are deter‐
mined automatically.
WIZ
Provides a step-by-step procedure for manual initialization of the valve.
Define the end positions manually.
WIZ
Enables the determination of the pneumatic leakage. The result is a stroke
movement as a %/minute caused by leakage.
WIZ
Speed test
Enables the determination of travel times in seconds.
WIZ
Enables the determination of an overshoot as a % in relation to the total
stroke. An overshoot of less than 3 % is displayed as "Ok".
WIZ
Sets the valve type. If "NONE" is displayed, no valve type is selected. When
a valve type is selected, the positioner is adapted to this valve type.
 
Selection of the application profile
AUTO
Enables the default setting, suitable for all applications.
TIGHT
Activates a control of the valve moves with maximum actuating force in the
end positions (close tight).
FAST
Enables dynamic control of the valve, optimized to a fast control response.
EXACT
Enables precise control of the valve.
ONOFF
Enables an open/closed behavior of the valve. The valve moves to the end
positions with maximum actuating force (close tight).
BOOST
Enables control of the valve with pneumatic booster.
SMALL
Enables control of a small valve with damped control response.
Operating Instructions, 06/2023, A5E50188938-AF
SIPART PS100