Parameter Settings - Mitsubishi Electric NZ2FTGN User Manual

Slice remote i/o module
Table of Contents

Advertisement

Parameter settings

The following table lists the parameters that can be set for the NZ2FTS-60RD4.
Item
General
Temperature unit
RTD 0 (Channel 0) to
Measurement range
RTD 3 (Channel 3)
Connection type
Conversion time
Channel diagnostics
Limit value monitoring
High limit value
Low limit value
*1 (0) to (18) are the values set in the register when the digital I/O module is connected to the NZ2FT-MT or the NZ2FT-EIP.
*2 Set values within the input range that was set in the parameter "Measurement range". For the range of the input range, refer to the
following.
Page 501 Measurement range
Description
Sets a unit of temperature (Celsius/Fahrenheit/Kelvin).
The specified unit of temperature is used for all channels.
Sets the input range for each channel according to the type
of the thermocouple to be connected.
Sets the connection method.
Set the conversion time to the RTD value for each channel.
The total of the actual conversion times of all channels is the
conversion cycle of the RTD value.
Sets Disabled (default).
Outputs an alert when a measurement value falls within the
alert output range set in advance.
The alert output range is set with "High limit value" and "Low
limit value".
Sets the upper limit value of the warning output (Process
*2
alarm).
Sets the lower limit value of the warning output (Process
*2
alarm).
*1
Setting range
• Degree Celsius (0)
• Degree Fahrenheit (1)
• Kelvin (2)
(Default: Degree Celsius)
• PT100 -200 ... 850 degree C (0)
• PT200 -200 ... 850 degree C (1)
• PT500 -200 ... 850 degree C (2)
• PT1000 -200 ... 850 degree C (3)
• NI100 -60 ... 250 degree C (4)
• NI120 -80 ... 260 degree C (5)
• NI200 -60 ... 250 degree C (6)
• NI500 -60 ... 250 degree C (7)
• NI1000 -60 ... 250 degree C (8)
• Cu10 -100 ... 260 degree C (9)
• Resistor 40 Ohm (10)
• Resistor 80 Ohm (11)
• Resistor 150 Ohm (12)
• Resistor 300 Ohm (13)
• Resistor 500 Ohm (14)
• Resistor 1000 Ohm (15)
• Resistor 2000 Ohm (16)
• Resistor 4000 Ohm (17)
• Disabled (18)
(Default: Disabled)
• 2-wire (0)
• 3-wire (1)
• 4-wire (2)
(Default: 2-wire)
• 240ms (0)
• 130ms (1)
• 80ms (2)
• 55ms (3)
• 43ms (4)
• 36ms (5)
(Default: 80ms)
• Disabled (0)
• Enabled (1)
(Default: Disabled)
• Disabled (0)
• Enabled (1)
(Default: Disabled)
• -32768 to 32767 (16-bit signed binary
value)
(Default: 32767)
• -32768 to 32767 (16-bit signed binary
value)
(Default: -32768)
18 TEMPERATURE INPUT MODULE
18.1 NZ2FTS-60RD4
18
505

Advertisement

Table of Contents
loading

Table of Contents