Confirmation by status information (Status word)

Check the Status word indicating the status of the NZ2FT-PN with the RJ71PN92 or Web server. ( Page 211 Input data)
Data configuration
The Status word is added to the start of Input data of each IO device by the GX Configurator-PN setting. ( Page 201
Device Library)
Bit
Item
Description
0
Error bit 0
System area
1 to 2
System area
3
Systembus error
Indicates the System bus status.
0: Normal
1: Error
4
Port 1 Link active
0: P1 link-down state
1: P1 link-up status
5
Port 2 Link active
0: P2 link-down state
1: P2 link-up status
6
I/O-Configuration
Displays the NZ2FT-PN configuration error.
error
0: Normal
1: Abnormal (There is a difference between the configuration information saved in the NZ2FT-PN and the current
configuration information.)
During I/O module replacement, this bit is set to 1 when the module is disconnected and is set to 0 when a new module is
mounted.
7
Master
Displays a configuration error.
configuration error
0: Normal
1: Abnormal (one of the following states)
• At the start of exchange, the pieces of I/O module configuration information in the actual I/O module configuration is less
• During operation, two pieces or more of I/O module configuration information were lacking in the actual I/O module
Since the NZ2FT-PN does not support safety standards, mounting an I/O module that supports safety standards will cause
an error.
8
MRP enabled
Not used (fixed to 1)
9
MRP role
Not used (fixed to 0)
10
Force mode active
0: Unexecuted
1: Force mode implemented
11 to 12
System area
13
Voltage U
error
Displays an error detected for the
OUT
external power supply voltage for output/
14
Voltage U
error
IN
input.
0: Normal
1: Abnormal (Power supply voltage is
less than 18VDC.)
15
Error bit 15
System area
than or does not match those held by the RJ71PN92. (The value remains at 0 if the pieces of I/O module configuration
information in the actual I/O module configuration is higher even after those held by the RJ71PN92 is included.)
configuration compared to those held by the RJ71PN92.
Power supply voltage (V)
Normal
18VDC
0
Voltage U
OUT
Normal
Voltage U
IN
Normal
Error
Error
9 NZ2FT-PN
9.9 Troubleshooting
9
223