Power Supply; Power Supply Derating - Mitsubishi Electric NZ2FTGN User Manual

Slice remote i/o module
Table of Contents

Advertisement

2.3

Power Supply

Power is supplied to all modules only by supplying power from the external power supply to the coupler and extension power
supply module.
The NZ2FT system has the U
circuit, and U
circuit for the system. If the current supplied to the entire NZ2FT system is insufficient, mount an extension
SYS
power supply module.
24V
24V
(1) When 24V power is supplied from the NZ2FTPDO, the previous U
(2) When 24V power is supplied from the NZ2FTPDI, the previous U
When designing the power supply, consider startup peaks.

Power supply derating

The power supply is restricted according to the ambient temperature.
Item
Supply power to the coupler
Supply power to the extension power
supply module
Precautions
• To compliant with UL 248-14, use a UL-approved Type-B automatic circuit breaker (such as ABB Type S201-B16) or use a
fuse with a maximum of 10A protection (such as ESKA Part No. 522.227). Using an inappropriate rated circuit protection
may cause failure.
• The auxiliary power supply, input signals, and output signals cannot be used for the power supply to the slave station.
Doing so may cause failure due to overcurrent.
circuit for supplying power to the output circuit, U
OUT
NZ2FTPDO
U
SYS
U
IN
U
OUT
(1)
OUT
and subsequent U
IN
For horizontal installation
• 60: 2  8A
• 55: 2  10A
• 60: 1  10A
circuit for supplying power to the input
IN
NZ2FTPDO
NZ2FTPDI
(1)
(2)
and subsequent U
are separated.
OUT
are separated.
IN
For vertical installation
• 55: 2  6A
• 50: 2  8A
• 55: 1  8A
2 OVERVIEW OF NZ2FT SYSTEM
2.3 Power Supply
2
31