Output value setting for fieldbus error

Set the output value of the I/O module for each case, such as when the CPU module status of the master station changes or
a fieldbus error occurs.
The output value changes depending on the following five settings.
 The master station CPU module device to be set at the RY refresh target of the NZ2FT-BT
 The following parameters of the master module
• RJ61BT11 "Output Mode upon CPU STOP": A "Send Remote Output (RY)", B "Send 0 data"
• QJ61BT11N "Case of CPU STOP Setting": A "Refresh", B "Clear compulsorily"
• FX5-CCL-MS "Output Mode upon CPU STOP": A "Send the output data", B "Send 0 data"
 NZ2FT-BT parameter "Output behaviour on fieldbus error"
 Parameter "Substitute value" for each I/O module
 The following parameters of the master module
• RJ61BT11 "Output Mode upon CPU Error"
• QJ61BT11N "PLC Down Select"
• FX5-CCL-MS "Output Mode upon CPU Error"
The data sent from the NZ2FT-C24 to the external device is not affected by the setting of  NZ2FT-GN parameter "Output
behaviour on fieldbus error".
For details on  and , refer to the following.
• RJ61BT11:  MELSEC iQ-R CC-Link System Master/Local Module User's Manual (Application)
• QJ61BT11N:  MELSEC-Q CC-Link System Master/Local Module User's Manual
• FX5-CCL-MS:  MELSEC iQ-F FX5 User's Manual (CC-Link)
Ex.
For the digital output module
Status of master station (RJ61BT11/
QJ61BT11N/FX5-CCL-MS)
 NZ2FT-BT RY refresh target: CPU
module device Y
 Master module parameters: no
effect
Data link in
CPU module RUN state
operation
CPU module: RUN  STOP
CPU module PAUSE state
When the CPU module is reset
When in CPU module stop error:
Follow .
Disconnected (fieldbus error occurred)
8 NZ2FT-BT
138
8.4 Functions
 NZ2FT-BT parameter "Output behaviour on fieldbus error" setting
0: All outputs off
1: Enable substitute value (A substitute
(All outputs are
value is output.)
turned off.)
 The I/O module
parameter
"Substitute value"
set to 1
Last
Last
Last
output
output
output
value is
value is
value is
off
on
off
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
 The I/O module
parameter
"Substitute value"
set to 0
Last
Last
Last
output
output
output
value is
value is
value is
on
off
on
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
2: Hold last value
(The last output
value is held.)
Last
Last
output
output
value is
value is
off
on
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
ON