Item
Connection
Network
Station type
Authentication Class
Number of connectable stations per master station
Input data size
Output data size
Parameter data
Number of connectable I/O modules (excluding extension power supply modules)
Setting interface
Communication speed
Transfer rate
External power supply voltage
Power supply rated current
Module current consumption
Power cable connection method
Applicable wire size
Weight
Precautions
The NZ2FT-GN supports only the following master modules.
Page 96 Corresponding master module and software package
Network ring connection, mesh connection, and communication speed of 100Mbps are not supported.

Block diagram

The following figure shows the internal block diagram of the NZ2FT-GN.
USB
8x
RJ45
RJ45
Fieldbus
System bus
Input power supply
Output power supply
Input power supply
Output power supply
μC
24VDC/10A Output
Specifications
2RJ45
CC-Link IE TSN
Remote station
Authentication Class B device
20 stations maximum
RX: 1024 points maximum
RWr: 512 points maximum
RY: 1024 points maximum
RWw: 512 points maximum
6464 bytes maximum
64 modules maximum
Micro USB 2.0
1Gbps maximum
48Mbps maximum
24VDC +20%/-15%
24VDC +20%/-15%
10A
10A
140mA
Spring clamp terminal block
Solid wire, stranded wire
0.14 to 1.5 (26 to 16 AWG)
234g