Example using the NZ2FTS-60RD4 (master module: RJ71EN71)

This program reads Process alarm data when Process alarm occurs in RTD 0 (Channel 0) to RTD 3 (Channel 3) of the
temperature input module.
System configuration
Item
Master station (IP address: 192.168.1.100)
Slave station (IP address: 192.168.1.200)
Device assignment
The following figure shows the device assignment for communication using the ECPRTCL instruction. ( Page 294
Checking warning output (Process alarm))
Master station
CPU module
D
W
D1000
W0
·
·
D1001
W1
11 NZ2FT-MT
342
11.9 Program Example of NZ2FT-MT
RJ71EN71
Power supply module
CPU module
Ethernet interface module
MODBUS/TCP coupler
4ch analog temperature input module (RTD)
RJ71EN71
Slave station
NZ2FT-MT
Input data
Byte
Content
0
Process alarm
·
data (4bytes)
4
NZ2FT-MT
Model
R61P
R04CPU
RJ71EN71
NZ2FT-MT
NZ2FTS-60RD4
NZ2FTS-60RD4
Process alarm data
Byte
Content
0
High alarm (1byte)
1
Low alarm (1byte)
2
16 Bit Time stamp
(2bytes)
3