Mitsubishi Electric NZ2FTGN User Manual page 206

Slice remote i/o module
Table of Contents

Advertisement

Item
Device
Name
Designation
Number
Link
Parameters
Active
Configuration
Network
IP Address
Properties
Device Name
9 NZ2FT-PN
204
9.6 Parameter Setting
Description
Set a name for each IO device to be used in GX Configurator-PN. The same name cannot be set for multiple IO devices. Use
a unique string such as NZ2FT_PN_001. (Default: NZ2FT_PN)
Select the IO device ID. IO device IDs are numbers used by the RJ71PN92 to manage IO devices. They are used to
distinguish IO devices by specifying the buffer memory bits.
■When checking "Link Parameters"
• IO device IDs are also used in the 4th octet of the NZ2FT-PN IP address. Therefore, select the IP address in the range of
"001" to "127" so that it does not overlap with the IP address of another IO device.
• When "000" is selected, the 4th octet of the IP address becomes 0, error code: FDH occurs in the RJ71PN92, and
communication cannot be performed.
■If "Link Parameters" is not checked
Select the IP address in the range of "000" to "127" so that it does not overlap with the IP address of another IO device.
Check the check box.
To set the 4th octet of the IP address in the range of 128 to 254, uncheck it.
Check the check box.
If "Link Parameters" is checked, it is automatically generated. The 1st to 3rd octets are the same value as those of the
RJ71PN92, and the 4th octet is the IO device ID set in "Number".
Since "nz2ft-pn" is displayed, change it to Device Name set in the "Name" text box on the "Devices on the Network" window.
( Page 202 Device Name setting)
Note that this is different from "Name" of "Device Designation" above.