Connection diagram
The following figure shows the connection diagram between the NZ2FTS3-4R and external devices.
Ex.
1
NC 0
2
COM 0
1
3
4
NO 0
1
NC 1
2
COM 1
2
3
4
NO 1
1
NC 2
2
COM 2
3
3
4
NO 2
1
NC 3
2
COM 3
4
3
4
NO 3
Controls up to 4 actuators with a 6A maximum. Power is supplied to the relay coil from the output current path (I
Precautions
When using the module in an environment where there is a risk of explosion, observe the following.
• Install the module in an environment without condensation, corrosives, or conductive dust.
• If the switching voltage or input voltage exceeds 63V, prepare a transient protection device that limits the peak voltage to
500V or less during transitions.
• Be sure that the temperature does not exceed the temperature class T4 limit, because the relay may wear out. Contact
resistance that exceeds 110m results in a failure.
• Use only resistive loads.
).
OUT
15 DIGITAL OUTPUT MODULE
15.7 NZ2FTS3-4R