Parameter settings
The following table lists the parameters that can be set for the NZ2FTS-60AD4.
Item
General
Frequency suppression
AI 0 (Channel 0) to
Data format
AI 3 (Channel 3)
Measurement range
*1 (0) to (8) are the values set in the register when the digital I/O module is connected to the NZ2FT-MT or the NZ2FT-EIP.
Process data
The following table lists the Process data of the NZ2FTS-60AD4.
Input/
Address
Output
(byte)
Input
0 to 1
2 to 3
4 to 5
6 to 7
16 ANALOG INPUT MODULE
484
16.1 NZ2FTS-60AD4
Description
Eliminates external noises through noise filtering.
Sets the resolution of AI values.
For the maximum resolution and AI value of each analog input range,
refer to the following.
Page 478 Input characteristics and maximum resolution
Switches the analog input range for each channel. Switching the range
changes I/O conversion characteristic too.
Description
AI 0 (Channel 0)
AI 1 (Channel 1)
AI 2 (Channel 2)
AI 3 (Channel 3)
*1
Setting range
• Disabled (0)
• 50Hz (1)
• 60Hz (2)
• Average over 16 values (3)
• 2Hz low pass (4)
(Default: Disabled)
• Normal resolution format (0)
• High resolution format (1)
(Default: High resolution format)
• 0 ... 20mA (0)
• 4 ... 20mA (1)
• 0 ... 10V (2)
• -10 ... 10V (3)
• 0 ... 5V (4)
• -5 ... 5V (5)
• 1 ... 5V (6)
• 2 ... 10V (7)
• Disabled (8)
(Default: Disabled)
Data format
Word
Word
Word
Word